ASTM E1105 Water Testing in Los Angeles

Thermal imaging shows you where water is. ASTM E1105 water testing proves exactly how it got there. Absolute Maintenance & Consulting performs standardized water penetration testing on residential and commercial buildings across Los Angeles to reproduce leaks under controlled conditions and confirm the exact point where water enters your building envelope.

ASTM E1105 is a testing standard published by ASTM International (formerly the American Society for Testing and Materials). It specifies exactly how to apply water to an exterior wall section and at what pressure, so results are repeatable, objective, and defensible. When we need to prove where a leak originates, not just suspect it, we deploy ASTM E1105 testing.

Cameron Figgins, founder of Absolute Maintenance & Consulting, has performed ASTM E1105 testing for over three decades on properties throughout Los Angeles County. We hold IICRC certification (#70018676) and CSLB license #998184. ASTM E1105 testing is available as a standalone service or as part of a comprehensive water intrusion investigation.

What Is the ASTM E1105 Water Test?

ASTM E1105 (“Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform or Cyclic Static Air Pressure Difference”) is a standardized procedure for testing whether water penetrates a building wall assembly under simulated rain conditions.

Here is what it does in plain language: we mount a calibrated spray rack on the outside of a wall section, apply water at a controlled rate (typically 5 gallons per square foot per hour), and observe the interior side for water penetration. The test runs for a specified duration, usually 15 minutes to 2 hours depending on the protocol, while we monitor the interior for any sign that water is passing through the wall assembly.

The standard includes two procedures:

  • Procedure A (Static pressure): Applies a constant air pressure differential across the wall while water is sprayed on the exterior. This simulates wind-driven rain. The pressure level is specified based on the building height and wind exposure.
  • Procedure B (No added pressure): Applies water spray only, without air pressure. This tests whether the wall leaks under gravity-driven water exposure alone. Procedure B is commonly used for residential investigations because it isolates the cladding and flashing performance from wind effects.

The result is binary: either water penetrates the wall assembly during the test, or it does not. When penetration occurs, we document exactly where on the interior the water appeared, the time elapsed before penetration, and the corresponding exterior location where water entered. This gives you a confirmed, defensible identification of the leak source.

Call: (310) 678-4345

When Do You Need ASTM E1105 Water Testing?

ASTM E1105 testing is not the first step in every investigation. It is the step you take when you need confirmation of a suspected leak source or when thermal imaging and moisture mapping have identified moisture but the exact entry point remains unclear.

You need ASTM E1105 testing when:

  • The leak only appears during rain and you cannot find the source. Thermal imaging and moisture meters detect moisture that is already present. ASTM E1105 recreates the rain event in a controlled, observable way so you can watch exactly where water enters.
  • A previous repair did not stop the leak. A contractor patched or sealed what they thought was the source, but water keeps coming back. ASTM E1105 testing on the repaired area confirms whether the repair worked or whether there is a second entry point.
  • Multiple possible sources exist. Your wall has stucco cracks, aging window sealant, and questionable flashing. ASTM E1105 testing isolates each element by testing one area at a time, from bottom to top, to identify which specific component is allowing water through.
  • You need documentation for an insurance claim or construction defect evaluation. ASTM E1105 results are standardized, repeatable, and recognized by insurance companies, engineers, and the legal system. The test protocol is codified, meaning another inspector can reproduce the same test and verify the results.
  • New construction warranty claim. Your new building has a leak and the builder disputes responsibility. ASTM E1105 testing provides objective evidence that water penetrates the wall assembly under standard rain simulation.
Call: (310) 678-4345

Call Us For Leak Detection Services

Residential ASTM E1105 Water Testing

For homeowners in Los Angeles, ASTM E1105 testing is most commonly deployed for:

Window and door leak confirmation. Windows are the most common source of water intrusion in Los Angeles homes, and many homes built between 1970 and 2000 lack proper sill pans and flashing. ASTM E1105 testing on a suspect window confirms whether water passes the window assembly under rain conditions. If it does, we can see exactly where, whether the sealant, the flashing, the sill pan, or the window frame itself is the failure point.

[Stucco wall](https://absolutemaintenanceconsulting.com/stucco-repair/) leak investigation. Stucco cracks are visible, but not every crack allows water through. ASTM E1105 testing determines which wall sections actively leak and which are cosmetic issues only. This prevents unnecessary repairs on areas that are not leaking while ensuring the actual problem areas get addressed.

Roof-to-wall transition testing. The junction where your roof meets your wall is one of the highest-risk areas for water intrusion. Missing kick-out diverters, improperly layered step flashing, and failed counter-flashing are common in LA construction. ASTM E1105 testing on these transitions confirms whether water is entering at the intersection.

Post-repair verification. After water intrusion repair work is completed, ASTM E1105 testing verifies that the repair actually stopped the leak. We recommend verification testing on every repair to confirm the work before you close up walls and finish surfaces.

Call: (310) 678-4345

Commercial ASTM E1105 Water Testing

Commercial buildings in Los Angeles have more complex building envelopes with more potential failure points. Absolute Maintenance & Consulting performs ASTM E1105 testing on:

  • Curtain wall systems where water penetration at mullion joints, spandrel panels, or anchor connections needs identification and documentation.
  • Storefront window assemblies in retail and mixed-use buildings where repeated leaking disrupts tenant operations and creates liability.
  • Multi-story stucco facades where testing isolates leaks floor by floor, starting at the bottom and working up to identify which floor level has the envelope failure.
  • New construction acceptance testing before the builder turns the project over to the owner. ASTM E1105 testing confirms that the building envelope performs to specification.
  • Construction defect claims where standardized test results provide the objective evidence needed for warranty disputes, insurance claims, and expert reporting.

Commercial ASTM E1105 reports from {BRAND} document the test setup, spray rack position, water application rate, duration, pressure (if applicable), observations, and results with timestamped photos. Reports are formatted for engineering review, insurance documentation, and construction defect proceedings.

Call: (310) 678-4345

Contact Our Water Intrusion Experts Today

The ASTM E1105 Test Procedure

Here is what happens during an ASTM E1105 test from Absolute Maintenance & Consulting:

Step

What Happens

1. Area Selection

We select the wall section(s) to test based on thermal imaging findings, moisture mapping data, and visual assessment of the exterior.

2. Interior Preparation

The interior side of the test area is exposed if needed (remove baseboards, access panels) so we can observe any water penetration in real time.

3. Spray Rack Installation

A calibrated spray rack is mounted on the exterior wall. The rack distributes water uniformly across the test area at the ASTM-specified rate of 5 gallons per square foot per hour.

4. Baseline Observation

We document the interior condition before testing begins: existing moisture readings, photos, and any pre-existing conditions.

5. Water Application

Water is applied to the exterior through the spray rack for the specified duration (typically 15 minutes to 2 hours). For Procedure A, air pressure is applied simultaneously.

6. Interior Monitoring

We observe the interior continuously for any sign of water penetration: visible water, new moisture meter readings above baseline, or changes visible on thermal imaging.

7. Sequential Testing

If multiple areas are suspect, we test from bottom to top. This prevents water from a higher test contaminating results below. Each area is tested separately.

8. Documentation

Results are documented with the test area location, rack position, water rate, duration, pressure (if used), time to first penetration, location of penetration, and photos.

 

Test duration varies by scope. A single window test takes approximately 45 minutes to 1 hour including setup. A multi-area investigation testing 3 to 5 wall sections takes half a day to a full day.

Call: (310) 678-4345

ASTM E1105 vs ASTM E331 vs AAMA 501: What Is the Difference?

Multiple ASTM and AAMA standards address water penetration testing. Here is how they differ:

Standard

What It Tests

Where It Is Used

Key Difference

ASTM E1105

Installed windows, doors, curtain walls, and wall assemblies in the field

On the actual building, after construction

Field test on the building as-built. Tests the real installation, not a sample.

ASTM E331

Window and door units in a laboratory setting

In a testing lab, before installation

Lab test on a window unit. Does not test how the window was installed in the wall.

AAMA 501.2

Installed window and curtain wall systems using a hose nozzle

On the actual building, after construction

Uses a handheld hose nozzle instead of a spray rack. Faster but less controlled than ASTM E1105.

For water intrusion investigations, ASTM E1105 is the standard we use because it tests the installed assembly in the field under controlled conditions. ASTM E331 results tell you that a window passed lab testing, not that the window as installed in your building is watertight. AAMA 501.2 (hose nozzle testing) is sometimes used as a quick screening test, but ASTM E1105 provides more uniform, repeatable results.

Call: (310) 678-4345

ASTM E1105 Testing Cost

Service

Price

Single area test (one window, one wall section)

Starting at $500

Multi-area testing (3-5 areas)

Starting at $1,200

Full building envelope test (commercial)

Custom quote

Post-repair verification test

Starting at $400 per area

 

ASTM E1105 testing is priced per test area because setup, duration, and complexity vary. Most residential investigations involve 1 to 3 test areas identified through thermal imaging and moisture mapping. We do not charge for testing areas that are clearly not leaking.

ASTM E1105 testing is often performed as part of a complete building envelope inspection. Call (310) 678-4345 to discuss your situation and get a specific quote.

Call: (310) 678-4345

Call Us For Leak Detection Services

Why Choose Absolute Maintenance & Consulting for ASTM E1105 Testing?

Three decades of field testing experience. Cameron Figgins has performed ASTM E1105 water penetration testing on hundreds of properties across Los Angeles County. He knows which wall assemblies, window types, and flashing details fail in LA construction and where to focus testing for the fastest, most accurate results.

Testing is part of our full investigation process. ASTM E1105 is most effective when paired with thermal imaging and moisture mapping. We do not test blindly. We use thermal imaging and moisture data to identify suspect areas first, then deploy ASTM E1105 to confirm.

We fix what we find. Unlike independent testing labs, Absolute Maintenance & Consulting both diagnoses and repairs water intrusion. We understand how wall assemblies fail because we take them apart and rebuild them. That repair knowledge makes us better diagnosticians.

Standardized, defensible results. Our ASTM E1105 reports follow the published standard protocol. Results are admissible for insurance claims, engineering review, warranty disputes, and construction defect evaluations.

Call: (310) 678-4345

Frequently Asked Questions

ASTM E1105 is a standardized field test for water penetration of installed exterior walls, windows, skylights, doors, and curtain walls. A calibrated spray rack applies water at a controlled rate (5 gallons per square foot per hour) to an exterior wall section while an observer monitors the interior for any water penetration. The test confirms whether and where water enters the building envelope.

Procedure A applies a static air pressure differential across the wall while water is sprayed on the exterior, simulating wind-driven rain. Procedure B applies water spray only without air pressure, testing whether the wall leaks under gravity-driven water exposure. Procedure B is commonly used for residential investigations because it isolates the cladding and flashing performance from wind effects.

A single area test takes approximately 45 minutes to 1 hour including setup. Multi-area investigations testing 3 to 5 wall sections take half a day to a full day. Water application duration is typically 15 minutes to 2 hours per test area depending on the protocol being followed.

No. ASTM E1105 applies water at rates that simulate normal rainfall. It does not exceed conditions your building would experience during a rain storm. If water penetrates during the test, it would also penetrate during real rain. In some cases, small exploratory openings on the interior are needed to observe penetration in real time, but we discuss any required openings with you before proceeding.

Yes. ASTM E1105 is a nationally recognized testing standard published by ASTM International. Test results are objective, repeatable, and standardized. Insurance adjusters, engineers, and attorneys recognize ASTM E1105 results as authoritative evidence of building envelope performance.

Start with a building envelope inspection that includes thermal imaging and moisture mapping. Most leaks are identified through those methods. ASTM E1105 is added when you need to confirm a specific entry point, verify a repair, document a defect for insurance or legal purposes, or when the source cannot be determined through non-invasive methods alone.

If you are buying property in Los Angeles, a building envelope inspection is strongly recommended. Standard home inspections do not include thermal imaging, moisture mapping, or water testing. Hidden water intrusion behind stucco, in crawl spaces, and around windows is common in LA construction and can mean thousands of dollars in repairs that a standard inspection misses. A pre-purchase building envelope inspection gives you the information you need to negotiate repairs or walk away.

Still have questions? Our experts are here to help.

Service Area

Absolute Maintenance & Consulting performs building envelope inspections throughout Los Angeles County, including West Los Angeles, Santa Monica, Venice, Culver City, Beverly Hills, Brentwood, Bel Air, Century City, Hollywood, Silver Lake, Echo Park, Pasadena, Glendale, Studio City, Sherman Oaks, Encino, and the South Bay communities.

Call (310) 678-4345 or email info@leakmoldrepair.com to schedule your building envelope inspection.

Call: (310) 678-4345
Don't Wait - Water Causes Damage Every Hour
Our emergency response team is standing by to repair your property and prevent further damage.